Default You Just Gotta Tighten Those Connections!

While it is hard to see the hardware for this CT, it was loose, never tightened. check the temperature of the spot, the hottest spot (not in this text was 266.6 F) The picture has been edited to remove the customer information. The black marks are magic marker and is utilized to obtain the temperature without the copper emistivity effecting the reading.



Last edited by brian john; 03-19-2007 at 04:51 PM.
brian john is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectrcianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
Old 03-19-2007, 04:54 PM   #2
Moderator
 
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,697
Default

Quote:
Originally Posted by brian john View Post
The black marks are magic marker and is utilized to obtain the temperature without the copper emistivity effecting the reading.
Can you talk a little more about that? That is, what is copper emmisivity, and how does it affect the reading if you don't scribble black marker on the buss tang?
MDShunk is online now   Reply With Quote
Old 03-19-2007, 06:01 PM   #3
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Leesburg VA
Posts: 6,501
Default

Marc:

I am not an IR thermographer and have limited knowledge on this subject, but basically it has to do with reflection of the surface which can skew the temperature. If I use the camera and look an a galvanized can I can see my image in the IR camera even though with a real time camera or my eye nothing is visible. Every substance (I believe) has an emissivity number.

From IEEE Dictionary:

Emissivity - The ratio of power radiated by a substance to the power radiated by a blackbody at the same temperature.
brian john is offline   Reply With Quote
Old 03-19-2007, 06:04 PM   #4
Member
 
rod213's Avatar
 
Join Date: Mar 2007
Location: West Virginia
Posts: 90
Default

Ah, I get it I think. You mark on it first with your marker so it doesn't reflect and you get a true temp reading with your IR? Otherwise itwould look like the rest of the area on that buss without the sharpie.

Interesting stuff there.
__________________
-Rodney
rod213 is offline   Reply With Quote
Old 03-19-2007, 06:50 PM   #5
Moderator
 
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,697
Default

Is this a special di-electric marker? Or an ordinary one from the office supply store? You don't have to answer that if it's a trouble making question. I was just wondering.
MDShunk is online now   Reply With Quote
Old 03-19-2007, 08:14 PM   #6
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Leesburg VA
Posts: 6,501
Default

Marc:

I'd rather not know...But yes it is a regular marker and I have warned him before..........But Steve says he has to do it to get a clear real picture. NOW PLEASE DO NOT REPEAT THIS it is strictly between you me and the rest...

I should have figured you'd pick up on this.
brian john is offline   Reply With Quote
Old 03-20-2007, 03:18 PM   #7
Senior Member
 
InControl's Avatar
 
Join Date: Mar 2007
Location: NY
Posts: 104
Default

We have yearly IR scans at the plant where I work. I've never heard of the black magic marker thing. I would think that it would give false high readings because the black would absorb heat.
InControl is offline   Reply With Quote
Old 03-20-2007, 04:48 PM   #8
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Leesburg VA
Posts: 6,501
Default

Just the opposite, it minimizes the reflection.

Are your thermographers Certified and electricians? Many thermographers are not electricians and while heat is heat have NOT A CLUE regarding electrical issues. Ie why there are thermal issues with a particular piece of equipment, Induction, bolted pressure switch issues...ECT.

Quote:
The ratio of power radiated by a substance to the power radiated by a blackbody at the same temperature
brian john is offline   Reply With Quote
Old 03-20-2007, 05:02 PM   #9
Senior Member
 
InControl's Avatar
 
Join Date: Mar 2007
Location: NY
Posts: 104
Default

We used to outsource our IR scans but our company is big enough that we had one of our electricians get sent out to get certified and the whole nine yards. I'll have to pick his brain when I get back to work.
InControl is offline   Reply With Quote
Reply

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
now we gotta compete with wiki nolabama Business, Marketing, and Sales 14 02-25-2010 04:46 PM
cleaning buss connections sparky970 General Electrical Discussion 8 09-03-2008 07:21 AM
12V Lighting Connections megavolt Lighting Design 11 04-18-2008 06:42 PM
You gotta pay attention brian john General Electrical Discussion 2 08-13-2007 04:38 PM
Handymen, gotta love em 3phase General Electrical Discussion 16 02-24-2007 07:45 PM

Top of Page | View New Posts

All times are GMT -4. The time now is 10:55 AM.


Electrician Talk © 2006 - 2009 The Building Network LLC

Search Engine Optimization by vBSEO 3.2.0