Working space violation, etc.
I hate to see new work with code violations. It gripes me even more to have other trades cause my compliant work to be in violation. Below is a picture of a service I built, only to have the HVAC man come in later years and put units right smack in the working space of the metering equipment. You can also barely make out the exposed bright orange #10 NM cable going to the handyman added AC disco on the right.
|
|
|
Join the #1 Electrician Forum Today - It's Totally Free!
ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!
Join ElectricianTalk.com - Click Here

|
Warning: The topics covered on this site include activities in which there exists the potential for serious injury
or death. ElectrcianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
01-13-2007, 07:38 PM
|
#2
|
|
Moderator
Join Date: Jan 2007
Location: NY State
Posts: 3,350
|
That whole thing is just criminal.
|
|
|
01-17-2007, 10:40 AM
|
#3
|
|
Member
Join Date: Jan 2007
Location: central Missouri
Posts: 98
|
At times I have considered having HVAC guys drawn and quartered, but people tell me that is a little harsh.
|
|
|
01-22-2007, 12:52 AM
|
#4
|
|
Senior Member
Join Date: Jan 2007
Posts: 132
|
Would it be wrong to report him for the violations? I been contemplating this question alot myself. I was brought up never to be a "rat" but as I am getting older the term dosent mean as much.
|
|
|
01-22-2007, 12:58 AM
|
#5
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,889
|
Quote:
Originally Posted by K&R
Would it be wrong to report him for the violations? I been contemplating this question alot myself. I was brought up never to be a "rat" but as I am getting older the term dosent mean as much.
|
I don't know. I struggle with the same question. Legally, no it wouldn't be wrong. Morally... that's another issuse. Pride plays into it a lot, I guess. As long as there's plenty of work for me, I'm not going to put up a fuss. Word gets out. If I ever have to scrap for work at some point in the future, I might be one mean dude in that regard. If I was out of work, I would not be beyond following people who just bought rolls of romex at home depot to see what they're doing with it. At the moment, I'm plenty busy, so I'll leave enforcement to somebody else. There have been two instances in the past in which the work being done or recently completed was so blatently and immediately hazardous that I fell compelled to turn it in. I guess we all have a line someplace in our head that shouldn't be crossed.
By the way, nice to have you here Ken.
|
|
|
01-22-2007, 01:35 AM
|
#6
|
|
Senior Member
Join Date: Jan 2007
Posts: 132
|
Thank's MD Im glad to be on here. I have read dozens of your posts and I asked you dozens of questions and have to say that in my time online or in the field you are one of the most knowledgeable electricians I have had the pleasure of talking to.
I guess where I am located at has alot to do with my question. I have seen some of the worst work done since relocating here 6 years ago then in my entire life. I would bet I could come up with 8-10 pics of code violations on every service call I go on or send my guys on. Some serious and some not so serious. I have seen unlicensed home improvment people do whole kitchens with 14-2 and not a single GFCI. I have watched licensed GC's (most respected GC's in the area)make flying splices in crawl spaces next to the shower drains to add a switch. I know of 1 licensed electrician that installs 1 feeder to a rooms center light (octagon box) and then does what I call (spider webs) out of that to power every thing in the entire room. We only have 1 inspector to cover the entire 622 sq. miles of our county. I have a problem turning them in. I guess as you say it's a moral issue. At the same time sooner or later someone will burn and die in one of these areas.
|
|
|
01-22-2007, 02:58 PM
|
#7
|
|
Member
Join Date: Jan 2007
Location: Long Beach, CA
Posts: 36
|
Marc, is that Seal Tite I see exiting the bottom of those 2 meter bases?
|
|
|
01-22-2007, 03:00 PM
|
#8
|
|
Member
Join Date: Jan 2007
Location: Long Beach, CA
Posts: 36
|
A little. Traditionally, they hung 'em 'bout halfway dead first. Then drew 'em an' quartered 'em.
Se
|
|
|
01-22-2007, 05:00 PM
|
#9
|
|
Senior Member
Join Date: Jan 2007
Location: Baltimore, MD, USA
Posts: 3,490
|
Whats trully annoying is that it wasn't nessasary at all to block the meters! Place that unit "in front of" the other, both facing to the right for access, and its golden.
|
|
|
01-22-2007, 05:25 PM
|
#10
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,889
|
Quote:
Originally Posted by lbwireman
Marc, is that Seal Tite I see exiting the bottom of those 2 meter bases?
|
What you're looking at there is 4/0 aluminium SE cable. It is traditional to do services in my area is SE cable, and PVC or RMC is an upsell. SE cable exposed is not considered "exposed to physical damage" by the inspection agency unless it's located right along a sidewalk, alleyway, parking lot, or similar.
Last edited by MDShunk; 01-22-2007 at 11:54 PM.
Reason: type-o
|
|
|
02-03-2007, 07:29 AM
|
#11
|
|
Senior Member
Join Date: Feb 2007
Location: Westchester County, NY
Posts: 194
|
Yes, lets someone know
Construction has grown in a furious pace in the last 2 decades or so. With that, there are many new installers/companies. There are also too many of them who are not aware of, or do not care of the requirements. As a contractor, you may be torn between "snitching" or keeping a contact with the customer. The way around this is to contact your inspector and let him/her deal with this.
As an inspector, what I have started doing in the last 6 months to combat this very issue is during the rough inspection, I contact the builder. I explain to him what the parameters of the location issues are and let him duke it out with the electrician and the HVAC guy. So far that seems to work pretty well.
|
|
|
02-03-2007, 12:42 PM
|
#12
|
|
NEC Educator & Consultant
Join Date: Jan 2007
Location: Harrisonburg,Va
Posts: 66
|
No Comment............
PS. Not directed at you Marc...I was gonna tease ya about supports on the SE Cable and SOMEONE took upon themselves to remove my post..SO I dont generally chat on overly controlled boards so....Enjoy and Best of LUCK !
__________________
Paul W. Abernathy,CME,RMS,CMI
Master Electrician/Electrical Educator/NEC Consultant
ICC & IAEI Certified Electrical Inspector/Plans Examiner
www.TheElectricalGuru.com
Last edited by TheElectricalGuru; 02-03-2007 at 01:16 PM.
Reason: ......You can remove my account Nathan !
|
|
|
02-03-2007, 01:23 PM
|
#13
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,889
|
Quote:
Originally Posted by TheElectricalGuru
..I was gonna tease ya about supports on the SE Cable
|
Those straps are "upside down", in my opinion also. I always put the screw below the cable or conduit, as I feel it makes for a more secure and longer lived install. I didn't install those straps personally. I was in the basement when they were being bolted on. It wasn't worth ordering it to be re-done differently, in my opinion. Doing odds and ends, like installing anchors and straps is a good thing for a helper to do. My oldest son, on that particular summer day. For SE cable risers, I've had guys alternate each strap to every-other side of the cable on the way up. I understand why this is done sometimes, but it looks "busy" to me, and I don't do it myself. I really don't hold it against a guy who does.
|
|
|
02-03-2007, 03:17 PM
|
#14
|
|
NEC Educator & Consultant
Join Date: Jan 2007
Location: Harrisonburg,Va
Posts: 66
|
lol..no my teasing was about having them supported at least 12" from the meter enclosure...lol...anyway was only teasing ya but someone obviously took it as more than that...lol....that photo has been edited since...lol...so ignore the teasing..
__________________
Paul W. Abernathy,CME,RMS,CMI
Master Electrician/Electrical Educator/NEC Consultant
ICC & IAEI Certified Electrical Inspector/Plans Examiner
www.TheElectricalGuru.com
|
|
|
02-03-2007, 06:35 PM
|
#15
|
|
Senior Member
Join Date: Jan 2007
Location: Salt Lake City
Posts: 617
|
Quote:
Originally Posted by JohnJ0906
Whats trully annoying is that it wasn't nessasary at all to block the meters! Place that unit "in front of" the other, both facing to the right for access, and its golden. 
|
The morons wouldn't have blocked the window that way either
__________________
Joe Momma was here
|
|
|
02-10-2007, 10:46 PM
|
#16
|
|
Member
Join Date: Feb 2007
Location: so. cal
Posts: 31
|
"I know of 1 licensed electrician that installs 1 feeder to a rooms center light (octagon box) and then does what I call (spider webs) out of that to power every thing in the entire room"
What's wrong with that.
|
|
|
02-10-2007, 11:58 PM
|
#17
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,889
|
Quote:
Originally Posted by sckeeth
"I know of 1 licensed electrician that installs 1 feeder to a rooms center light (octagon box) and then does what I call (spider webs) out of that to power every thing in the entire room"
What's wrong with that.
|
Nothing, as long as the box fill rules are observed. That is an older style of wiring, mostly done in the 60's and 70's. Not normally practiced today, but nothing wrong with it as long as you mind your box fill rules. When rooms are wired in EMT, it's still a normal method.
Not sure how this applies to this thread, though.
|
|
|
| Thread Tools |
Search this Thread |
|
|
|
| Display Modes |
Linear Mode
|
Posting Rules
|
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts
HTML code is Off
|
|
|
|
|