Default #10 XLPE 125C Wire Ampacity?

I'm installing a 40A electric range and the wires in the appliance whip (attached to the range) are #10 XLPE 125C.

I can't find XLPE in the 2008 NEC though several posts on this site indicate I should see it 310.15 - 310.21 tables. I googled XLPE and it looks like it is used in automobiles.

Table 310.16 says various #10 wires rated at 90C are good for 40A but I don't see XLPE in the wire type heading.

Do I need to replace this whip with #8 wire or am I good to go?

Thanks

__________________
Elvis is in the building
swimmer is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
Old 07-29-2012, 11:16 AM   #2
BBQ
Senior Member
 
BBQ's Avatar
 
Join Date: Nov 2010
Location: New England
Posts: 23,912
Default

If it is a UL listed range cord the NEC does not apply and you are free to use it.

BBQ is online now   Reply With Quote
Old 07-29-2012, 11:17 AM   #3
Electric Al
 
oldtimer's Avatar
 
Join Date: Jun 2010
Location: Canada
Posts: 4,063
Default

Quote:
Originally Posted by swimmer View Post
I'm installing a 40A electric range and the wires in the appliance whip (attached to the range) are #10 XLPE 125C.

I can't find XLPE in the 2008 NEC though several posts on this site indicate I should see it 310.15 - 310.21 tables. I googled XLPE and it looks like it is used in automobiles.

Table 310.16 says various #10 wires rated at 90C are good for 40A but I don't see XLPE in the wire type heading.

Do I need to replace this whip with #8 wire or am I good to go?

Thanks



I M O, if the equipment came complete, and is UL or (in my case CSA) approved. Then you should be good to go.
__________________
I'd rather have a bottle in front of me , than a frontal lobotomy. ( Quote from Tom Waits. )
oldtimer is offline   Reply With Quote
Old 07-29-2012, 12:48 PM   #4
Swimmer
 
swimmer's Avatar
 
Join Date: Mar 2011
Location: California
Posts: 304
Default

Quote:
Originally Posted by oldtimer View Post
I M O, if the equipment came complete, and is UL or (in my case CSA) approved. Then you should be good to go.

The range had been returned to Sears and re-sold at discount. Besides this, it is new.
Proper flex connector was missing from the conduit and ground and neutral were crimped together. This makes me question the wire size. It's no problem for me to attach a #8 whip but I'd like to know about this XLPE 125C business as this may be something I'll encounter in the future.
__________________
Elvis is in the building
swimmer is offline   Reply With Quote
Old 07-29-2012, 01:19 PM   #5
Sideways Sparky
 
farlsincharge's Avatar
 
Join Date: Dec 2010
Location: SK Canada
Posts: 809
Default

It stands for cross linked polyethylene. Very common up here. Don't overthink it too much.
farlsincharge is offline   Reply With Quote
Reply

Tags
125c, xlpe ampacity

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Xlpe/use TheBrushMan007 NEC Code Forum 11 04-14-2011 02:02 PM
240.4B2 breakered above wire ampacity??? 1capybara NEC Code Forum 20 01-08-2011 02:57 PM
Installation Rate/Pulling Rate for Single 630mm2 76/132Kv XLPE/SWA custy General Electrical Discussion 0 01-25-2010 01:42 AM
metric sized wire & ampacity chart BryanMD UK Electrical Forum 6 12-08-2008 03:00 PM
What is the ampacity for 8 AWG wire? 50 or 40 gilamor NEC Code Forum 23 10-19-2008 09:28 PM

Top of Page | View New Posts

All times are GMT -4. The time now is 07:14 AM.


Electrician Talk © 2006 - 2010 The Building Network

Search Engine Optimization by vBSEO 3.6.0 RC 2