Old 05-19-2008, 08:04 AM   #1
Registered Member
 
Join Date: May 2008
Location: spain
Posts: 3
Default Problems with a halogen ceeling set up

Hi,

I hope im posting in the correct forum.

My experience with electrics is very limited.

I am having problems with a lighting set up i bought from Ikea.
It is a 5 halogen system, a twin wire that connects to opposite sides of the wall running across the ceeling with a transformer to connect to before going into the mains. The halogens run along the wiring between the 2 cables and are powered by pins that push into the cable.

Problem is this, when i switch the thing on, the lights barely light up, just a very dim orange glow and then they go off imediatley. I tried it with only one bulb connected to a shorter piece of cable off the wall, the same problem happens.

Does anyone know what this could be?

I have called Ikea and they said to bring it back, the problem is Ikea is a 5 hour drive from my house.

Any advise appreciated.

Dave
pilky78 is offline  
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectrcianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
Old 05-19-2008, 08:08 AM   #2
Seen your member
 
480sparky's Avatar
 
Join Date: Sep 2007
Location: Cornpatch USA
Posts: 9,962
Default

Box it up and ship it back to them.
__________________
This message is hidden because Forgery, Honda Racer, JackBoot, LawnGuyLandSparky, milehiwire and user 5941 are on your ignore list.
480sparky is offline  
Old 05-19-2008, 08:29 AM   #3
Registered Member
 
Join Date: May 2008
Location: spain
Posts: 3
Default

Thanks Sparky but i don't have time.
I need to get it sorted asap.

Dave
pilky78 is offline  
Old 05-19-2008, 01:05 PM   #4
Happy as a Goat herd.
 
Ecopat's Avatar
 
Join Date: Apr 2008
Location: Exeter
Posts: 320
Default

Ditto on Sparkies advice, I take this is a SELV transformer running 12/24v?
__________________
"Quid non Resolutio"
Ecopat is offline  
Old 05-19-2008, 01:16 PM   #5
Registered Member
 
Join Date: May 2008
Location: spain
Posts: 3
Default

Yes i think it is a 12v.
I was hoping one of you guys would know what the problem was through the explanation.

Im thinking its something im doing wrong but i have followed all the instructions.

Dave
pilky78 is offline  
Old 05-19-2008, 03:26 PM   #6
Happy as a Goat herd.
 
Ecopat's Avatar
 
Join Date: Apr 2008
Location: Exeter
Posts: 320
Default

The thing is, it sounds to me like you have a typical IKEA scenario, I take it the terminals for the lampholders are cup shaped with a grub screw that you do up to A) Hold the lampholders in place and B) Make the electrical connection?
If so and you have power, as you said "They glow then go off" The SELV Transformer is failing to do what it is desaigned to do and is therefore faulty and probably was before it left the factory.
Likely case scenario is that after it was checked and prior to it being packaged for shipment it somehow got damaged, could have been dropped etc,etc.
The only thing you can do is what Sparky first suggested, take it back to where you got it, they "IKEA" have this happen a lot over here in the UK, so I guess it's the same in the US.

Sorry that I cant be much more help than that, but in my proffessional opinion this is the only option open to you.
You shouldnt have any problems exchanging it, consumer rights and all the other.
Nige.
__________________
"Quid non Resolutio"
Ecopat is offline  
Old 05-19-2008, 05:44 PM   #7
Moderator
 
Join Date: Jan 2007
Location: NY State
Posts: 3,350
Default

Thanks for posting on ElectricianTalk.com. The Moderators/Admin of this forum would prefer if you post Do It Yourself related topics on our sister site www.DIYChatroom.com

As stated in the sign up page, ElectricianTalk.com is designed for electrical industry professionals to discuss issues and topics related to the electrical trades and related industries. Many of our professionals are also members at DIYChatroom.com and are looking forward to assist you with your needs.

Please take a moment to post your question at
www.DIYChatroom.com If your not already a member of DIYChatroom.com you can sign up for a free account by going to http://www.diychatroom.com/register.php/
Speedy Petey is offline  
Closed Thread

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
former employer problems tjl General Electrical Discussion 22 11-16-2008 08:11 PM
Outdoor Lighting - LED vs. Halogen philsig Tools, Equipment and New Products 2 01-09-2008 05:39 AM
Furnace problems calimurray General Electrical Discussion 10 01-05-2008 08:53 PM
Tripping problems giarc84 General Electrical Discussion 4 12-20-2007 02:57 PM
RCBO Problems jonny_know_it Structured Wiring 2 09-24-2007 07:39 AM

Top of Page | View New Posts

All times are GMT -4. The time now is 01:54 AM.


Electrician Talk © 2006 - 2009 The Building Network LLC

Search Engine Optimization by vBSEO 3.2.0