Generator Issues
Got a service call today from a local Police Department.. They had another electrical company install a back up generator (15kw Generac), They are now having a problem with there ups it keeps burning up. After testing it a bit seems that the ups is going from regular power to battery back up like every second that the generator is running. I'm assuming that is due to the "dirty" power. Anyone ever run into this problem? Any suggestions to what we can do to solve this? Im thinking along the lines of installing a power conditioner... Open for suggestions!!!
|
|
|
Join the #1 Electrician Forum Today - It's Totally Free!
ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!
Join ElectricianTalk.com - Click Here

|
Warning: The topics covered on this site include activities in which there exists the potential for serious injury
or death. ElectrcianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
08-20-2009, 04:33 AM
|
#2
|
|
Senior Member
Join Date: Jan 2009
Location: Washington
Posts: 246
|
The UPS should have a sensitivity button on the back that will allow it to run with the "dirty" power. Had the same problem happen to us, it solved it
|
|
|
08-20-2009, 08:30 AM
|
#3
|
|
B4T Scotchkote installer
Join Date: Feb 2009
Location: Long Island, N.Y.
Posts: 4,500
|
Did you call GENERAC tech support and ask them??
|
|
|
08-20-2009, 12:15 PM
|
#4
|
|
Senior Member
Join Date: Jan 2009
Location: Washington
Posts: 246
|
They'd just send a replacement engine
|
|
|
08-20-2009, 05:46 PM
|
#5
|
|
Journeyman Electrician
Join Date: Jan 2008
Location: massachusetts
Posts: 1,387
|
im not sure on the exact math but i believe you need to size the generator much larger than the UPS system. UPS systems can cause problems on undersized generators contact generac and they will tell you exactly what to do
|
|
|
08-20-2009, 09:35 PM
|
#6
|
|
Member
Join Date: May 2009
Location: Nature Coast of Florida
Posts: 89
|
did you do a frequency test?
|
|
|
08-23-2009, 07:21 AM
|
#7
|
|
Junior Member
Join Date: Aug 2009
Location: Ontario
Posts: 5
|
Quote:
Originally Posted by Sparky480
Got a service call today from a local Police Department.. They had another electrical company install a back up generator (15kw Generac), They are now having a problem with there ups it keeps burning up. After testing it a bit seems that the ups is going from regular power to battery back up like every second that the generator is running. I'm assuming that is due to the "dirty" power. Anyone ever run into this problem? Any suggestions to what we can do to solve this? Im thinking along the lines of installing a power conditioner... Open for suggestions!!!
|
You need to go get training to work on these units. (It may be half assed but you will void their warranty)
The company who sold them the unit screwed up...
Air Cooled units do not work with UPS systems.
They require a new generator. Liquid cooled.
http://www.msaenterprises.ca/generators.html
they have a pricing list available, the password is public.
|
|
|
08-23-2009, 10:13 AM
|
#8
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,942
|
Quote:
Originally Posted by iamatt
Air Cooled units do not work with UPS systems.
They require a new generator. Liquid cooled.
|
 Because the UPS knows whether the generator has a radiator or not?  Ya...
__________________
|
|
|
08-23-2009, 11:22 AM
|
#9
|
|
B4T Scotchkote installer
Join Date: Feb 2009
Location: Long Island, N.Y.
Posts: 4,500
|
Quote:
Originally Posted by MDShunk
 Because the UPS knows whether the generator has a radiator or not?  Ya...
|
yea.. NOW that makes sense
|
|
|
08-23-2009, 11:29 AM
|
#10
|
|
Moderator
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 6,942
|
Quote:
Originally Posted by Black4Truck
yea.. NOW that makes sense 
|
I think it's more of an admission on some manufacturer's part, basically saying, "we make our air-cooled generators to such sloppy specifications, that you need to use one of our liquid-cooled generators to get clean power". I believe this is true, for the most part.
A good generator will be liquid-cooled and run at 1800 rpm.
__________________
|
|
|
08-23-2009, 11:44 AM
|
#11
|
|
Senior Member
Join Date: Feb 2008
Location: Atlanta, Ga/Hamilton, Al
Posts: 2,035
|
I believe switch 4 on the DIP switch on the control board controls whether the generator runs at 60 Hz, or at 58-62 Hz.
On = 60 Hz. Try that.
|
|
|
08-23-2009, 02:50 PM
|
#12
|
|
Junior Member
Join Date: Aug 2009
Location: Ontario
Posts: 5
|
Quote:
Originally Posted by MDShunk
 Because the UPS knows whether the generator has a radiator or not?  Ya...
|

Really eh...
Anyways. The air cooled units suck.
They can not run a UPS. The freq is bad.
No UPS likes the units. Some UPS are adjustable. But for the most part, they just do not work.
Goto a liquid cooled unit and everything will be cleaned up.
You will not have any issues with UPS with the liquid cooled units.
|
|
|
08-23-2009, 04:57 PM
|
#14
|
|
B4T Scotchkote installer
Join Date: Feb 2009
Location: Long Island, N.Y.
Posts: 4,500
|
Bob.. great links and you do a good job of "myth busting"
|
|
|
08-23-2009, 09:18 PM
|
#15
|
|
Senior Member
Join Date: Jan 2009
Location: Washington
Posts: 246
|
Quote:
Originally Posted by iamatt
Anyways. The air cooled units suck.
|
Generac blows in general
|
|
|
08-25-2009, 08:32 AM
|
#16
|
|
Senior Member
Join Date: Jun 2009
Location: Manchester, Verrmont
Posts: 171
|
Generac blow in general. They're cheap, and there parts are cheap.
What does the power generator sign-wave look like?
That where I would start, before going on to the UPS.
|
|
|
08-25-2009, 05:50 PM
|
#17
|
|
Senior Member
Join Date: Jun 2009
Location: Manchester, Verrmont
Posts: 171
|
Here is a web address you can go to. I understand this company may be
able to assist you.
www.purepowerAPS.com/