Old 04-30-2012, 03:30 PM   #1
Senior Member
 
JmanAllen's Avatar
 
Join Date: Aug 2011
Location: Oklahoma
Posts: 935
Default Service change out

Thought I would post some pics of a service change out I did and remember I'm real a commercial guy so be easy on me

Notice the one lug that has 2 wire under it in the old meter. I was called out at 1st because after they would kill the main part of the kitchen still ha power that wire ran to a old federal main lug panel in the middle of the house that they didn't know about
Attached Images
File Type: jpg image-966000088.jpg (113.0 KB, 54 views)
File Type: jpg image-2727657499.jpg (112.4 KB, 48 views)
File Type: jpg image-1782570491.jpg (115.6 KB, 55 views)
File Type: jpg image-3141786555.jpg (112.5 KB, 65 views)
File Type: jpg image-2686301274.jpg (109.8 KB, 54 views)

JmanAllen is offline   Reply With Quote
The Following User Says Thank You to JmanAllen For This Useful Post:
Magnettica (05-01-2012)
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!
Old 04-30-2012, 04:54 PM   #2
Heavily Armed Member
 
HARRY304E's Avatar
 
Join Date: Sep 2010
Location: Fascistchusetts
Posts: 29,483
Default

Quote:
Originally Posted by JmanAllen View Post
Thought I would post some pics of a service change out I did and remember I'm real a commercial guy so be easy on me

Notice the one lug that has 2 wire under it in the old meter. I was called out at 1st because after they would kill the main part of the kitchen still ha power that wire ran to a old federal main lug panel in the middle of the house that they didn't know about
Looks good..

Looks like the old service was under the siding>>

HARRY304E is online now   Reply With Quote
Old 04-30-2012, 06:53 PM   #3
Good at being Evil
 
Shockdoc's Avatar
 
Join Date: Mar 2010
Location: Long Island,NY & Poconos
Posts: 11,119
Default

That feed out the back of the pan is a hell of a Rube Goldberg.Nice makeover.
__________________
All these liberal laws has turned me into a right wingnut..
Shockdoc is offline   Reply With Quote
Old 04-30-2012, 07:31 PM   #4
Senior Member
 
JmanAllen's Avatar
 
Join Date: Aug 2011
Location: Oklahoma
Posts: 935
Default

Quote:
Originally Posted by HARRY304E

Looks good..

Looks like the old service was under the siding>>
Yes it was and the weather head was in the eve covered up
JmanAllen is offline   Reply With Quote
Old 04-30-2012, 07:53 PM   #5
Registered Member
 
Join Date: Jan 2009
Location: N.E.
Posts: 16,081
Default

It's pics like these that make me glad that I don't do work in rural areas.
user4818 is offline   Reply With Quote
Old 04-30-2012, 08:03 PM   #6
976-EVIL
 
mcclary's electrical's Avatar
 
Join Date: Feb 2009
Location: State of Euphoria
Posts: 13,408
Default

wouldn't pass here.
mcclary's electrical is offline   Reply With Quote
Old 04-30-2012, 08:04 PM   #7
still in business
 
sbrn33's Avatar
 
Join Date: Mar 2007
Location: middle america
Posts: 2,625
Default

Should have entered on the bottom side below the live parts.
__________________
Stop trying to think logically, it won't help you here. Just do as we say and everything will be alright.
sbrn33 is offline   Reply With Quote
The Following 2 Users Say Thank You to sbrn33 For This Useful Post:
Awg-Dawg (04-30-2012), mcclary's electrical (04-30-2012)
Old 04-30-2012, 09:47 PM   #8
Senior Member
 
JmanAllen's Avatar
 
Join Date: Aug 2011
Location: Oklahoma
Posts: 935
Default

Quote:
Originally Posted by Peter D
It's pics like these that make me glad that I don't do work in rural areas.
It was a decent size town about 8000 people.
JmanAllen is offline   Reply With Quote
Old 04-30-2012, 09:48 PM   #9
Senior Member
 
JmanAllen's Avatar
 
Join Date: Aug 2011
Location: Oklahoma
Posts: 935
Default

Quote:
Originally Posted by sbrn33
Should have entered on the bottom side below the live parts.
And the taken the feeders all the way around the inside that makes no scene

JmanAllen is offline   Reply With Quote
Reply

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
200-amp service change BIGRED Services and Service Equipment 24 08-23-2011 07:51 PM
Change service or not dgorack Commercial Electrical Forum 5 08-16-2011 10:34 PM
Service change GEORGE D Residential Electrical Forum 4 06-19-2011 12:54 PM
Service Change NolaTigaBait General Electrical Discussion 47 12-10-2010 10:11 PM
AZ service change. 220/221 General Electrical Discussion 64 04-17-2009 06:25 PM

Top of Page | View New Posts

All times are GMT -4. The time now is 09:50 AM.


Electrician Talk © 2006 - 2010 The Building Network

Search Engine Optimization by vBSEO 3.6.0 RC 2