Old 10-02-2018, 10:31 AM   #1
Junior Member
 
Join Date: Nov 2017
Location: Texas
Posts: 6
Rewards Points: 12
Default Bolt on Panel conversion

Does anyone know if Schneider Electric makes a part to change a QOB buss bar to QO bar?
Dauphin is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 10-02-2018, 10:42 AM   #2
Senior Member
 
sbrn33's Avatar
 
Join Date: Mar 2007
Location: middle america
Posts: 11,438
Rewards Points: 3,276
Default

OK, I gotta ask what would make you ever want to do that?
Bird dog likes this.
sbrn33 is offline   Reply With Quote
Old 10-02-2018, 11:54 AM   #3
Junior Member
 
Join Date: Nov 2017
Location: Texas
Posts: 6
Rewards Points: 12
Default

Quote:
Originally Posted by sbrn33 View Post
OK, I gotta ask what would make you ever want to do that?
To be able to change out breakers from the buss without unscrewing from the buss bar. I thought they made an adapter that screws in to the buss bar to make it accept QO breakers.
Dauphin is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 10-02-2018, 03:31 PM   #4
Wire Ninja
 
MDShunk's Avatar
 
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 20,984
Rewards Points: 1,421
Default

They make an adapter to put QO breakers in an I-Line panel. Most QOB panels are actually QOD panels (QO-dual), and they'll take either bolt-on or plug-on breakers. The only part to convert a straight QOB panel to a QO panel is called a new panel interior. I think doing so, and the motivations for such, are extremely unwise and ill-advised.
__________________
One reason not to give DIY advice:
Catch a man a fish and you can sell it to him.
Teach a man to fish and you’ve ruined a good business opportunity.
MDShunk is offline   Reply With Quote
Old 10-02-2018, 04:07 PM   #5
Senior Member
 
just the cowboy's Avatar
 
Join Date: Sep 2013
Location: Pa
Posts: 1,607
Rewards Points: 404
Default

Think safety!!! You are going backwards and looking to work hot. Them days are gone, even just pushing a breaker into a hot panel is not a good practice anymore.


You list yourself as industrial, think that way bigger boom.


Good luck
Cowboy
__________________
A cowboy may get thrown down, but he always gets up and walks forward and don't look back at what thru him.
just the cowboy is offline   Reply With Quote
Old 10-03-2018, 07:19 AM   #6
Junior Member
 
Join Date: Nov 2017
Location: Texas
Posts: 6
Rewards Points: 12
Default

The panels I’m working with now are NTFB 44235 electrical panels with bolt on fused breakers. I’m looking to upgrade all 25 panels with QO breakers. I’m not interested in working on live circuits but the nature of my work, being able to change out breakers more quickly is a big plus. I did buy a NQ442L2C however this panel interior did not fit with the way it was originally wired. I was looking for other ideas to be able to convert them all to QO breakers.

More notes these fused breakers are failing. The plastic is brittle and the internals of them are heating up probably due to their age.
just the cowboy likes this.
Dauphin is offline   Reply With Quote
The Following User Says Thank You to Dauphin For This Useful Post:
just the cowboy (10-03-2018)
Old 10-03-2018, 08:25 AM   #7
Wire Ninja
 
MDShunk's Avatar
 
Join Date: Jan 2007
Location: Beautiful Cumberland Valley, in PA
Posts: 20,984
Rewards Points: 1,421
Default

The old NTFB panelboards have ordinary QOB bus fingers. I'm confused as hell why you insist on wanting to change to QO breakers. That's going backwards with no benefit other than satisfying your hard head. You actually had an NQOD/NQ panelboard interior and were's savvy enough to install it. Maybe you're not cut out for this electrician thing? Although I've never tried to convert a QOB panel to a QOD panel, I'd imagine the SKNQOD225 kits are what you'd need. They're the renewal kit for burned up bus fingers in an NQOD panel. They might actually work on QOB busing. I have no idea, though.
__________________
One reason not to give DIY advice:
Catch a man a fish and you can sell it to him.
Teach a man to fish and you’ve ruined a good business opportunity.

Last edited by MDShunk; 10-03-2018 at 08:49 AM.
MDShunk is offline   Reply With Quote
Old 10-03-2018, 09:41 AM   #8
Senior Member
 
just the cowboy's Avatar
 
Join Date: Sep 2013
Location: Pa
Posts: 1,607
Rewards Points: 404
Default Think duty

Quote:
Originally Posted by Dauphin View Post

More notes these fused breakers are failing. The plastic is brittle and the internals of them are heating up probably due to their age.

This is one reason to stay with bolt-on, in my opinion QO are for homes, bolt on for industry because of the continuous load and heating.


Cowboy
__________________
A cowboy may get thrown down, but he always gets up and walks forward and don't look back at what thru him.
just the cowboy is offline   Reply With Quote
Old 10-03-2018, 10:51 AM   #9
Junior Member
 
Join Date: Nov 2017
Location: Texas
Posts: 6
Rewards Points: 12
Default

Quote:
Originally Posted by MDShunk View Post
The old NTFB panelboards have ordinary QOB bus fingers. I'm confused as hell why you insist on wanting to change to QO breakers. That's going backwards with no benefit other than satisfying your hard head. You actually had an NQOD/NQ panelboard interior and were's savvy enough to install it. Maybe you're not cut out for this electrician thing? Although I've never tried to convert a QOB panel to a QOD panel, I'd imagine the SKNQOD225 kits are what you'd need. They're the renewal kit for burned up bus fingers in an NQOD panel. They might actually work on QOB busing. I have no idea, though.
Thats what i was looking for. Thanks Mr. MDSkunk
Dauphin is offline   Reply With Quote
Old 10-03-2018, 01:01 PM   #10
Senior Member
 
sbrn33's Avatar
 
Join Date: Mar 2007
Location: middle america
Posts: 11,438
Rewards Points: 3,276
Default

I have been in this a long time. I have seen fused breakers exactly twice.
sbrn33 is offline   Reply With Quote
Old 10-03-2018, 02:47 PM   #11
Junior Member
 
Join Date: Nov 2017
Location: Texas
Posts: 6
Rewards Points: 12
Default

Quote:
Originally Posted by sbrn33 View Post
I have been in this a long time. I have seen fused breakers exactly twice.
Well almost every panel where i am has fused breakers. These panels are from when the building was constructed in the 70's. Im going to go panel by panel and change them to QO style if this part works out.
Dauphin is offline   Reply With Quote
Old 10-03-2018, 03:08 PM   #12
Senior Member
 
Join Date: May 2015
Location: Sacramento, California
Posts: 13,810
Rewards Points: 25,866
Default

That's just crazy.

QOB !
telsa is offline   Reply With Quote
Old 10-03-2018, 03:45 PM   #13
Senior Member
 
sbrn33's Avatar
 
Join Date: Mar 2007
Location: middle america
Posts: 11,438
Rewards Points: 3,276
Default

Quote:
Originally Posted by Dauphin View Post
Well almost every panel where i am has fused breakers. These panels are from when the building was constructed in the 70's. Im going to go panel by panel and change them to QO style if this part works out.
That is a thermal magnetic breaker not fused.
If you change out those QOB's to QO you should be fired.
There are a lot of good electricians on here and not one of them thinks that is a good idea.

I am starting to think thins is a troll thread.
sbrn33 is offline   Reply With Quote
Old 01-01-2019, 02:50 PM   #14
Senior Member
 
Join Date: Mar 2007
Posts: 793
Rewards Points: 1,058
Default

A panel from the '70's would be QOB only, since they were only slightly different then the '60's panels, even if they could use QO, plug-in, QOB,bolt-on breakers are still the better choice.
Norcal is offline   Reply With Quote
Reply

Tags
qo power panel, qob

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
low voltage security panel mounting gpop Other Codes and Standards 5 10-17-2018 03:23 PM
New Main Panel in Residence dalizardking427 Residential Electrical Forum 6 09-15-2018 08:51 AM
Need advice for mouting a pony panel NDC Canadian Electrical Forum 10 04-05-2018 02:52 PM
Double panel design question. JohnJ65 Services and Service Equipment 23 07-07-2017 08:19 PM
Bolt in or snap in panel? five.five-six General Electrical Discussion 27 05-26-2017 11:07 PM


All times are GMT -4. The time now is 06:51 AM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2019, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com