Old 10-09-2019, 04:58 PM   #1
Junior Member
 
Join Date: Oct 2019
Posts: 1
Rewards Points: 2
Default Remotely-triggerable 3 phase power switch

Hi,

I am looking for a way to cut power to an instrument operating on 208V 3phase <=24 Amps.

I was going to use a watchdog relay to trigger a switch, but I am not finding a UL certified switch available. Does anyone know of such a device?
dangordon is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 10-09-2019, 05:58 PM   #2
Bilge Rat
 
Join Date: Aug 2007
Location: Fernley, Nevada (near Reno)
Posts: 6,903
Rewards Points: 3,414
Default

If by 'switch' you mean 'relay', there are tons of them that are UL listed and will handle a 208 3Ø 24 amp load.

Just about any motor starter comes to mind but there are others as well.
micromind is offline   Reply With Quote
Old 10-09-2019, 06:11 PM   #3
Hackenschmidt
 
splatz's Avatar
 
Join Date: May 2015
Location: Parts Unknown
Posts: 10,102
Rewards Points: 2,836
Default

That watchdog relay is a specialized thing, do you have a means of generating the pulse it looks for?
__________________
Life is short, and work long, opportunity fleeting, experiments dangerous, and judgment hard.
splatz is online now   Reply With Quote
Sponsored Links
Advertisement
 
Old 10-09-2019, 06:11 PM   #4
Senior Member
 
460 Delta's Avatar
 
Join Date: May 2018
Location: Southern Ohio
Posts: 1,319
Rewards Points: 1,986
Default

Are you wanting to trip it on an over current? Or am I reading this wrong? As @micromind said, a NEMA 1 starter of your brand choice is ready and willing to take on the task. If silent operation is required, DC coils are available.
__________________
Overkill Is Underrated
460 Delta is online now   Reply With Quote
Old 10-09-2019, 07:53 PM   #5
Senior Member
 
Join Date: May 2018
Location: florida
Posts: 2,279
Rewards Points: 2,778
Default

Shunt trip breaker?
gpop is online now   Reply With Quote
Old 10-09-2019, 08:12 PM   #6
Beam Me Up Scotty
 
Kevin_Essiambre's Avatar
 
Join Date: Feb 2017
Location: Ottawa, Ontario, Canada
Posts: 1,997
Rewards Points: 470
Default

Three phase disconnect. Hire a guy to stand beside it with a pager. Every time you want the disconnect activated (either on or off), page him, and he flips the switch on the disconnect.

This is by far the easiest way to go.

P.S., please fill out your profile.

Sent from my Samsung using Tapatalk
Flyingsod likes this.
__________________
Vote Kevin for Moderator!
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
Kevin_Essiambre is online now   Reply With Quote
Old 10-09-2019, 08:21 PM   #7
Senior Member
 
Join Date: May 2018
Location: florida
Posts: 2,279
Rewards Points: 2,778
Default

Quote:
Originally Posted by dangordon View Post
Hi,

I am looking for a way to cut power to an instrument operating on 208V 3phase <=24 Amps.

I was going to use a watchdog relay to trigger a switch, but I am not finding a UL certified switch available. Does anyone know of such a device?
First time i read that im trying to picture a pressure sensor or flow meter hooked to 208.

Then he mentioned watchdog which a plc term for checking if a processor has frozen which it probably would if you put 208 to a analog card so im just posting to get my post count higher so i can donate it to what ever that thing is they do once a year.

Guessing i would say this is a e-stop question using all the wrong words.
gpop is online now   Reply With Quote
Old 10-09-2019, 08:30 PM   #8
Senior Member
 
460 Delta's Avatar
 
Join Date: May 2018
Location: Southern Ohio
Posts: 1,319
Rewards Points: 1,986
Default

Quote:
Originally Posted by gpop View Post
First time i read that im trying to picture a pressure sensor or flow meter hooked to 208.

Then he mentioned watchdog which a plc term for checking if a processor has frozen which it probably would if you put 208 to a analog card so im just posting to get my post count higher so i can donate it to what ever that thing is they do once a year.

Guessing i would say this is a e-stop question using all the wrong words.
Seems to me that watchdog was a term that Westinghouse or GE used for the Klixon imbedded in the windings in motors and xformers to signal an over temp situation. Maybe this is what he’s speaking of.
And + two points. But I’m keeping mine!
gpop and John R like this.
__________________
Overkill Is Underrated
460 Delta is online now   Reply With Quote
Old 10-09-2019, 09:10 PM   #9
Senior Member
 
Join Date: May 2018
Location: florida
Posts: 2,279
Rewards Points: 2,778
Default

Quote:
Originally Posted by 460 Delta View Post
Seems to me that watchdog was a term that Westinghouse or GE used for the Klixon imbedded in the windings in motors and xformers to signal an over temp situation. Maybe this is what he’s speaking of.
And + two points. But I’m keeping mine!
I had to google Klixon. I learnt a cool sounding new word today so that's worth 2 points. Ive always referred to them as thermal switch's.
460 Delta and John R like this.
gpop is online now   Reply With Quote
Old 10-09-2019, 09:32 PM   #10
Bilge Rat
 
Join Date: Aug 2007
Location: Fernley, Nevada (near Reno)
Posts: 6,903
Rewards Points: 3,414
Default

I've known them as Klixons for 45 years.......
micromind is offline   Reply With Quote
Old 10-09-2019, 09:50 PM   #11
Hackenschmidt
 
splatz's Avatar
 
Join Date: May 2015
Location: Parts Unknown
Posts: 10,102
Rewards Points: 2,836
Default

Red Lion makes a watchdog relay, which looks for a heartbeat pulse from the PLC. A high or low signal may continue if the PLC hangs, but a flip flop / heartbeat means the program must still be running.

https://www.redlion.net/sites/defaul...ta%20Sheet.pdf
__________________
Life is short, and work long, opportunity fleeting, experiments dangerous, and judgment hard.
splatz is online now   Reply With Quote
Old 10-09-2019, 10:57 PM   #12
Senior Member
 
Wardenclyffe's Avatar
 
Join Date: Jan 2019
Location: Georgia
Posts: 361
Rewards Points: 756
Default

Quote:
Originally Posted by Kevin_Essiambre View Post
Three phase disconnect. Hire a guy to stand beside it with a pager. Every time you want the disconnect activated (either on or off), page him, and he flips the switch on the disconnect.

This is by far the easiest way to go.

P.S., please fill out your profile.

Sent from my Samsung using Tapatalk
Defeat the interlock and tie a rope and pulley on it,...
Attached Images
 
Kevin_Essiambre likes this.
Wardenclyffe is online now   Reply With Quote
Old 10-10-2019, 05:04 AM   #13
Senior Member
 
460 Delta's Avatar
 
Join Date: May 2018
Location: Southern Ohio
Posts: 1,319
Rewards Points: 1,986
Default

Quote:
Originally Posted by micromind View Post
I've known them as Klixons for 45 years.......
Yeah but we are like old and stuff so.......
micromind likes this.
__________________
Overkill Is Underrated
460 Delta is online now   Reply With Quote
Old 10-10-2019, 06:25 AM   #14
Chief Flunky
 
Join Date: Oct 2017
Location: Carolinas
Posts: 1,380
Rewards Points: 366
Default

Isn’t it just a timer delay relay with normally closed contacts? I know AB has a universal one and I’m sure Macromatic does too.

The Klixon brand covers a huge variety of let’s just say motor accessories. Thermistors, thermal switches, centrifugal switches. Mostly stuff the motor shop epoxies or bolts inside then runs extra wires out to the peckerhead. It’s all chintzy looking but for whatever reason holds up, except RTDs. Why anyone builds anything to protect something that isn’t far more reliable than the thing it protects is beyond me. Motor RTD designers should be ashamed of themselves. Their solution is that they’re cheap so buy lots and buy an RTD reader with a dozen inputs so you can trip by majority voting logic. Oh that makes sense. Kind of like let’s install 6 breakers for one circuit because well you know, one or two will go bad.


Sent from my iPhone using Tapatalk
paulengr is offline   Reply With Quote
Old 10-10-2019, 09:11 PM   #15
Senior Member
 
JRaef's Avatar
 
Join Date: Mar 2009
Location: SF Bay Area, California
Posts: 5,339
Rewards Points: 558
Default

Square D used to make a load shedding system called a "Watchdog"...


I think until the OP checks back in and defines what he/she meant by "watchdog relay", we can go on guessing for days, maybe weeks.
__________________
"If you don't know where you're going, then any direction will do." -- Lewis Carroll
JRaef is offline   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off



All times are GMT -4. The time now is 07:17 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2020, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com