Here's some pics of a 6 unit we did about 3 yrs ago, happen to drive by today and I know you guys like pics. Long story but we were having some trouble with our local inspector not allowing us to use a 6 pack meter unit, so here's what we did
Attached Thumbnails
6 unit service-image-54079868.jpg  

6 unit service-image-1140879202.jpg  

6 unit service-image-3399662772.jpg  

6 unit service-image-1817739642.jpg  

ohiosparky99 is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 04-03-2012, 10:07 PM   #2
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Probably should have put a mast and weatherhead up for the phone and cable but we didn't
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:12 PM   #3
Senior Member
 
Awg-Dawg's Avatar
 
Join Date: Jan 2007
Location: Dayton Ohio
Posts: 3,342
Rewards Points: 704
Default

Quote:
Originally Posted by ohiosparky99 View Post
Here's some pics of a 6 unit we did about 3 yrs ago, happen to drive by today and I know you guys like pics. Long story but we were having some trouble with our local inspector not allowing us to use a 6 pack meter unit, so here's what we did

I never do this stuff, but why cant you use a meter bank?

Also, are discos just inside wall?
__________________
I feel sorry for people who don't drink, when they wake up in the morning, that's the best they will feel all day.
Awg-Dawg is online now   Reply With Quote
Sponsored Links
Advertisement
 
Old 04-03-2012, 10:12 PM   #4
Member
 
Join Date: Oct 2010
Location: maryland
Posts: 74
Rewards Points: 77
Default

Hey I never did a service head splice how do u do it.. is there a bug kit or somthing or in line splice
brianthejabroni2 is offline   Reply With Quote
Old 04-03-2012, 10:16 PM   #5
Senior Member
 
Hairbone's Avatar
 
Join Date: Feb 2011
Location: Upstate New York
Posts: 528
Rewards Points: 500
Default

WOW
__________________
BORN TO FISH... FORCED TO WORK

FISH ON
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
Hairbone is offline   Reply With Quote
Old 04-03-2012, 10:17 PM   #6
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by brianthejabroni2
Hey I never did a service head splice how do u do it.. is there a bug kit or somthing or in line splice
The PUCO does it here, but occasionally we do our own, we use Blackburn crimps and a O/D crimper by Kearny
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:18 PM   #7
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by Awg-Dawg

I never do this stuff, but why cant you use a meter bank?

Also, are discos just inside wall?
No, those are meter mains, "disc is under meter in the same can"
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:22 PM   #8
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by ohiosparky99

No, those are meter mains, "disc is under meter in the same can"
Also, we have a really hard headed inspector that said since we have 6 200 amp panels that the bus rating on the 6 pack had to be 1200 amps which is crazy, you can't even buy a 6 pack with that rating and we actually had a square D rep
call him and explain the derating for a multi-family but he was too hard headed to listen, so instead of arguing we did it this way, cheaper in the long run
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:23 PM   #9
Senior Member
 
Awg-Dawg's Avatar
 
Join Date: Jan 2007
Location: Dayton Ohio
Posts: 3,342
Rewards Points: 704
Default

Quote:
Originally Posted by ohiosparky99 View Post
No, those are meter mains, "disc is under meter in the same can"

Ok, I get it now.

Gawdy, but work looks good.

I agree a meter pack would have been easier to do.
__________________
I feel sorry for people who don't drink, when they wake up in the morning, that's the best they will feel all day.
Awg-Dawg is online now   Reply With Quote
Old 04-03-2012, 10:28 PM   #10
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

This used to be a 6 bay car wash, they added 10' to the back and made 600' sq ft' apartments, I know, why 200 amp services but that's what the owner wanted
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:28 PM   #11
Senior Member
 
Cletis's Avatar
 
Join Date: Aug 2010
Location: georgia
Posts: 10,316
Rewards Points: 2,050
Default port

I bet thats the best looking service in portsmouth! and I know portsmouth believe me
__________________

To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.


I'm shakin it boss..I'm shakin it
Cletis is offline   Reply With Quote
Old 04-03-2012, 10:36 PM   #12
Senior Member
 
Awg-Dawg's Avatar
 
Join Date: Jan 2007
Location: Dayton Ohio
Posts: 3,342
Rewards Points: 704
Default

Quote:
Originally Posted by ohiosparky99 View Post
Also, we have a really hard headed inspector that said since we have 6 200 amp panels that the bus rating on the 6 pack had to be 1200 amps
Does he apply the same logic to panels?
__________________
I feel sorry for people who don't drink, when they wake up in the morning, that's the best they will feel all day.
Awg-Dawg is online now   Reply With Quote
Old 04-03-2012, 10:40 PM   #13
Senior Member
 
Join Date: Mar 2012
Location: Colorado
Posts: 427
Rewards Points: 434
Default

Why not set a gutter above the Meter Mains and run one mast up the wall?
JHFWIC is offline   Reply With Quote
The Following User Says Thank You to JHFWIC For This Useful Post:
Salvatoreg02 (04-04-2012)
Old 04-03-2012, 10:44 PM   #14
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by JHFWIC
Why not set a gutter above the Meter Mains and run one mast up the wall?
Yeah, we had thought about that, but would have needed a lug for 7 conductors, figured by the time we spliced it, bought lugs, wireway, and all the other stuff, we could just do it this way and be done
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:46 PM   #15
Senior Member
 
Cletis's Avatar
 
Join Date: Aug 2010
Location: georgia
Posts: 10,316
Rewards Points: 2,050
Default 5th

Was that in the 5th ward? It looks like one of those new developments on ports
__________________

To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.


I'm shakin it boss..I'm shakin it
Cletis is offline   Reply With Quote
Old 04-03-2012, 10:49 PM   #16
Senior Member
 
360max's Avatar
 
Join Date: Jun 2011
Location: NY
Posts: 11,434
Rewards Points: 1,234
Default

Nice pipework !! Whats up with the couplings 2' from the weather heads?

Last edited by 360max; 04-03-2012 at 10:58 PM.
360max is offline   Reply With Quote
Old 04-03-2012, 10:52 PM   #17
Senior Member
 
Join Date: Apr 2009
Location: NC
Posts: 1,287
Rewards Points: 530
Default

Nice work man! Obvious a craftsman did it.
GEORGE D is offline   Reply With Quote
Old 04-03-2012, 10:57 PM   #18
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by Cletis
Was that in the 5th ward? It looks like one of those new developments on ports
Actually New Boston area, a few miles east of Portsmouth
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 10:59 PM   #19
Senior Member
 
Join Date: Nov 2009
Location: portsmouth, ohio
Posts: 741
Rewards Points: 534
Default

Quote:
Originally Posted by 360max
Whats up with the couplings 2' from the weather heads?
Was hoping you wouldn't zoom in and see that, actually didn't think about it until after we bent the pipe then it was a little too late
ohiosparky99 is offline   Reply With Quote
Old 04-03-2012, 11:04 PM   #20
Senior Member
 
Awg-Dawg's Avatar
 
Join Date: Jan 2007
Location: Dayton Ohio
Posts: 3,342
Rewards Points: 704
Default

Quote:
Originally Posted by ohiosparky99 View Post
Was hoping you wouldn't zoom in and see that, actually didn't think about it until after we bent the pipe then it was a little too late

Too late now.

You're a hack.
__________________
I feel sorry for people who don't drink, when they wake up in the morning, that's the best they will feel all day.
Awg-Dawg is online now   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
multi unit service ToddH General Electrical Discussion 2 02-01-2012 01:10 PM
85 ton a/c unit B W E General Electrical Discussion 8 12-09-2011 12:40 PM
unit pricing Zparme Business, Marketing, and Sales 8 04-30-2011 08:34 PM
first four dwelling unit service upgrade jpimentel84 General Electrical Discussion 50 02-19-2011 09:29 PM
9 unit plus house 800 amp 1 phase service gemini13 Services and Service Equipment 60 08-12-2009 12:31 AM


All times are GMT -4. The time now is 09:09 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2019, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com