#1 |
Member
Join Date: Jan 2014
Location: USA
Posts: 96
Rewards Points: 105
|
![]()
I recently had a job inspected and all the old work was done quite sloppily. Specifically wires not stapled and running across across the joists. I failed inspection because of it and now am in the process of lengthening the old wires so I can staple them to the joists. I am wondering though is that specifically a code or just the inspectors subjective interpretation of neat work?
|
![]() |
![]() |
![]() |
Join the #1 Electrician Forum Today - It's Totally Free! ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free! |
Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task! |
Sponsored Links | |||
Advertisement |
|
![]() |
#2 | |
Senior Member
Join Date: Feb 2011
Location: mn
Posts: 12,376
Rewards Points: 296
|
![]() Quote:
|
|
![]() |
![]() |
![]() |
#3 |
Petulant Amateur
Join Date: Aug 2012
Location: Perky Nipples, Canada
Posts: 21,002
Rewards Points: 12,371
|
![]()
Here is how I understand it in general terms: An inspector cannot demand upgrades to a building for wiring that was original. If it is obvious that there was wiring done after the fact that was not properly permitted and inspected, he can demand that it be brought up to current standards.
Our job quotes state that we do not include repairs to existing wiring in our bid. Safety concerns and violations will be brought to the attention of the owner or GC and will be quoted separately. If an inspector demands repairs and upgrades, that's money in the bank ![]() |
![]() |
![]() |
The Following User Says Thank You to 99cents For This Useful Post: | RIVETER (01-26-2014) |
Sponsored Links | |||
Advertisement |
|
![]() |
#4 |
Member
Join Date: Jan 2014
Location: USA
Posts: 96
Rewards Points: 105
|
![]()
Hmm good to know. I may just fix it all. Halfway through already. Some of the old work is stapled but it's on top of the joist. That shouldn't be a problem should it?
|
![]() |
![]() |
![]() |
#5 | |
Senior Member
Join Date: Feb 2011
Location: mn
Posts: 12,376
Rewards Points: 296
|
![]() Quote:
|
|
![]() |
![]() |
![]() |
#6 | |
Petulant Amateur
Join Date: Aug 2012
Location: Perky Nipples, Canada
Posts: 21,002
Rewards Points: 12,371
|
![]() Quote:
If you're getting paid for all this extra work it could be a nice little money maker ![]() |
|
![]() |
![]() |
![]() |
#7 |
Senior Member
Join Date: Dec 2012
Location: SE WI
Posts: 2,923
Rewards Points: 2,024
|
![]()
320.23 via 334.23
|
![]() |
![]() |
![]() |
#8 |
corn-fused
Join Date: Jun 2013
Location: on the river, near the corn
Posts: 4,769
Rewards Points: 620
|
![]()
it can stay on top if its protected, such as a strip of wood on both sides
__________________
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts. i like neat! just doesnt always happen To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts. |
![]() |
![]() |
The Following User Says Thank You to papaotis For This Useful Post: | chicken steve (01-26-2014) |
![]() |
#9 |
Senior Member
Join Date: Dec 2012
Location: SE WI
Posts: 2,923
Rewards Points: 2,024
|
![]()
Only necessary if the attic is accessible by permanent stairs or within 6' of the scuttle.
|
![]() |
![]() |
![]() |
#10 |
Member
Join Date: Jan 2014
Location: USA
Posts: 96
Rewards Points: 105
|
![]()
Ok so what do they mean by guard strips in the code book?
|
![]() |
![]() |
![]() |
#11 |
Member
Join Date: Jan 2014
Location: USA
Posts: 96
Rewards Points: 105
|
![]()
And I didn't pull the permits
|
![]() |
![]() |
![]() |
#12 |
Electrical Contractor
Join Date: Sep 2010
Location: Wisconsiberia
Posts: 9,327
Rewards Points: 54
|
![]()
The big question is: is the attic accessed by a permanent stair or ladder. If not, protection is only needed within 6' of the access hole. I believe the guard strips would be strips of 1x4 or something of the like nailed on each side of the cable to protect it when you're back up there redoing someone's work. It must be at least as thick as the cable.
__________________
Saving the world, one backstabbed receptacle at a time. To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts. |
![]() |
![]() |
![]() |
#13 |
Member
Join Date: Jan 2014
Location: USA
Posts: 96
Rewards Points: 105
|
![]()
Thanks for everyone's input. So there are not permanent stairs. So that means wires already stapled on the face not within 6 ft are ok, right? In addition I can stop stapling all these wires? I'm not getting paid for the extra work unfortunetly
|
![]() |
![]() |
![]() |
#14 |
Petulant Amateur
Join Date: Aug 2012
Location: Perky Nipples, Canada
Posts: 21,002
Rewards Points: 12,371
|
![]()
I would stop stapling and work on your power of negotiation.
|
![]() |
![]() |
The Following User Says Thank You to 99cents For This Useful Post: | dspiffy (01-26-2014) |
![]() |
#15 |
:-)
Join Date: Nov 2012
Location: Alberta
Posts: 3,670
Rewards Points: 2,382
|
![]()
We don't care where the access is. If there is a meter (3 ft. + 3 inches or so ) clearance we protect our wire. I always wire near the outside walls so don't worry about protection.
Staple at one end then walk 40 or so feet to the other end and pull her tight. Eye ball within a 16th of an inch for square and drop a second staple. Two wires under a staple. If I'm feeling chipper I might toss another staple in here or there when doing the general wiring of the room. My rough-in (all at right angles) looks wonderful. Always the inspector smiles and has never once asked where the ladder is.
__________________
<< To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts. I like perfect. To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts. |
![]() |
![]() |
![]() |
Display Modes |
![]() |
![]() |
![]() |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
Running EMT in attic | Aegis | General Electrical Discussion | 24 | 08-28-2012 09:50 PM |
Rewiring 2nd floor from the attic; wires and attic floorboards | Breakfasteatre | Residential Electrical Forum | 14 | 01-08-2012 11:00 AM |
Correcting wires ran incorrectly along floor joists | cmdietz | NEC Code Forum | 11 | 08-27-2011 04:12 PM |
running NMSC through holes in joists question | LTH306 | Residential Electrical Forum | 5 | 03-31-2011 10:14 PM |
Wires in the attic... | waco | General Electrical Discussion | 5 | 09-08-2008 10:11 PM |