Old 09-15-2017, 08:56 PM   #1
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Gilbert's Corner VA
Posts: 29,908
Rewards Points: 1,588
Default You Gotta Pay Attention

We were performing some MV testing yesterday to try and ascertain what the issue was at a site when they went to generator 10 seconds into the test, boom.

Seems the generator had the wrong pots and voltage regulator, voltage went extremely high and the Surge Arrestors blew.

Are farts lumpy?
Attached Thumbnails
You Gotta Pay Attention-img_5373.jpg  

You Gotta Pay Attention-img_5374.jpg  

__________________
Ah, but I was so much older then, I'm younger than that now
brian john is offline   Reply With Quote
The Following User Says Thank You to brian john For This Useful Post:
hardworkingstiff (09-15-2017)
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 09-15-2017, 09:10 PM   #2
Modérateur
 
frenchelectrican's Avatar
 
Join Date: Mar 2007
Location: Philippines
Posts: 8,635
Rewards Points: 16,782
Default

Nice smoking show .,,

what voltage and size the generator it was set up on ?
__________________
Bleu est beau.
frenchelectrican is offline   Reply With Quote
Old 09-15-2017, 09:16 PM   #3
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Gilbert's Corner VA
Posts: 29,908
Rewards Points: 1,588
Default

Quote:
Originally Posted by frenchelectrican View Post
Nice smoking show .,,

what voltage and size the generator it was set up on ?
400 kw at 2400 V Delta, stepped up to 13.2 kv for distribution this switch was 13.
frenchelectrican likes this.
__________________
Ah, but I was so much older then, I'm younger than that now

Last edited by brian john; 09-15-2017 at 09:44 PM.
brian john is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 09-15-2017, 09:24 PM   #4
Modérateur
 
frenchelectrican's Avatar
 
Join Date: Mar 2007
Location: Philippines
Posts: 8,635
Rewards Points: 16,782
Default

Quote:
Originally Posted by brian john View Post

400 kw at 240o V Delta, stepped up to 13.2 kv for distribution this switch was 13.2
Ouch .,, not cheap service call for sure .,,
__________________
Bleu est beau.
frenchelectrican is offline   Reply With Quote
Old 09-16-2017, 12:33 AM   #5
Cow
Senior Member
 
Join Date: Jan 2008
Location: Eastern Oregon
Posts: 2,877
Rewards Points: 4,590
Default

The kind of service calls you get Brian sound EXPENSIVE!!
MechanicalDVR likes this.
Cow is offline   Reply With Quote
Old 09-16-2017, 12:41 AM   #6
Senior Member
 
Join Date: Jun 2010
Location: Brisbane, Australia.
Posts: 2,869
Rewards Points: 2,372
Default

So who has to pay to clean up the mess and restore everything
Not cheap I am sure !

dmxtothemax is offline   Reply With Quote
Old 09-16-2017, 01:46 AM   #7
Old Grumpy Bastard
 
MechanicalDVR's Avatar
 
Join Date: Dec 2007
Location: "Old Dominion"
Posts: 59,297
Rewards Points: 1,010
Default

Glad nobody was hurt.
brian john likes this.
__________________
I'm as Christian as possible in the times we live in.

Always just a stallion in a china shop
MechanicalDVR is online now   Reply With Quote
Old 09-16-2017, 04:16 AM   #8
Senior Member
 
Join Date: Jun 2010
Location: Brisbane, Australia.
Posts: 2,869
Rewards Points: 2,372
Default

One pair of jocks ruined !
dmxtothemax is offline   Reply With Quote
Old 09-16-2017, 06:57 AM   #9
Small Potatoes
 
flyboy's Avatar
 
Join Date: Jun 2011
Location: North East USA Treasure Coast Florida
Posts: 4,950
Rewards Points: 3,636
Default

Quote:
Originally Posted by dmxtothemax View Post
One pair of jocks ruined !
Dry fit rince out nicely and if you hold them out the window of a moving vehicle dry quickly.
brian john likes this.

Last edited by flyboy; 09-16-2017 at 07:16 AM.
flyboy is online now   Reply With Quote
Old 09-16-2017, 07:26 AM   #10
86 45 20
 
Southeast Power's Avatar
 
Join Date: Jan 2009
Location: Florida
Posts: 17,738
Rewards Points: 8,152
Default

Quote:
Originally Posted by brian john View Post

400 kw at 2400 V Delta, stepped up to 13.2 kv for distribution this switch was 13.
So, the surge arresters did their job?
Did the unit have fuses?
Was it a new installation?
Southeast Power is offline   Reply With Quote
Old 09-16-2017, 09:17 AM   #11
Senior Member
 
brian john's Avatar
 
Join Date: Mar 2007
Location: Gilbert's Corner VA
Posts: 29,908
Rewards Points: 1,588
Default

Quote:
Originally Posted by Southeast Power View Post
So, the surge arresters did their job?
Did the unit have fuses?
Was it a new installation?
Surge arrestors diid their job, there were fuses CB tripped back at main service.
__________________
Ah, but I was so much older then, I'm younger than that now
brian john is offline   Reply With Quote
Old 09-16-2017, 09:44 PM   #12
Senior Member
 
Join Date: Jun 2010
Location: Brisbane, Australia.
Posts: 2,869
Rewards Points: 2,372
Default

It wasn't me Boss !
Honestly !

Name:  kick butt.png
Views: 86
Size:  11.1 KB
dmxtothemax is offline   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
ATTENTION Florida! Did the pv panels stay put? macmikeman Alternative Energy Forum 3 09-13-2017 08:40 AM
Gotta get through this brick Jamato Commercial Electrical Forum 32 08-09-2017 03:36 AM
Maj, you gotta take today off! 99cents Off Topic (Non Trade) 18 06-03-2017 03:56 AM
Attention - Password And Security Update admin Site Help and Suggestions 253 12-13-2016 12:11 AM


All times are GMT -4. The time now is 06:35 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2019, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com