Old 06-24-2015, 11:39 PM   #1
Senior Member
 
Join Date: May 2014
Location: youfigureitout
Posts: 112
Rewards Points: 184
Default Old work fixture support box??

I do a lot of high end kitchens with pendants over islands and locating them exactly during the rough is next to impossible since sometimes they get moved to make walkways larger. I usually leave coils of wire in the ceiling and let the rockers cover it, then cut in old work ceiling boxes on the final. I haven't had any issues with inspectors until now, he's calling me out on the fact that they're not rated for a fixture. how is everyone else going about this? I'm always open to new ideas. Thx
NJSparky is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 06-24-2015, 11:42 PM   #2
corn-fused
 
papaotis's Avatar
 
Join Date: Jun 2013
Location: on the river, near the corn
Posts: 4,769
Rewards Points: 620
Default

depends on the weight of the fixture. if the arent rated for a fixture what are they for?
__________________

To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
i like neat! just doesnt always happen
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
papaotis is offline   Reply With Quote
Old 06-24-2015, 11:47 PM   #3
Senior Member
 
Join Date: May 2014
Location: youfigureitout
Posts: 112
Rewards Points: 184
Default

Straight from Carlon's website
What is the weight limit for your old work round box #B618R if you are
hanging a light fixture from the ceiling.
The B618R is a round old work outlet box and is not listed for fixture support in
the ceiling. Only approved ceiling boxes are allowed to support fixtures in the
ceiling. These boxes will be permitted to support a minimum weight of 50
pounds. The B618R can be used in the ceiling as a junction box. Do not hang a
fixture from it since it relies on the strength of the ceiling itself
NJSparky is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 06-24-2015, 11:47 PM   #4
Senior Member
 
backstay's Avatar
 
Join Date: Feb 2011
Location: mn
Posts: 12,376
Rewards Points: 296
Default

If you're talking about a blue winged box, they are not listed for fixture support.
backstay is offline   Reply With Quote
Old 06-24-2015, 11:50 PM   #5
corn-fused
 
papaotis's Avatar
 
Join Date: Jun 2013
Location: on the river, near the corn
Posts: 4,769
Rewards Points: 620
Default

and those answered my question. satisfied?
__________________

To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
i like neat! just doesnt always happen
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
papaotis is offline   Reply With Quote
Old 06-24-2015, 11:56 PM   #6
Senior Member
 
Join Date: May 2015
Location: Sacramento, California
Posts: 14,057
Rewards Points: 26,360
Default

Quote:
Originally Posted by NJSparky View Post
I do a lot of high end kitchens with pendants over islands and locating them exactly during the rough is next to impossible since sometimes they get moved to make walkways larger. I usually leave coils of wire in the ceiling and let the rockers cover it, then cut in old work ceiling boxes on the final. I haven't had any issues with inspectors until now, he's calling me out on the fact that they're not rated for a fixture. how is everyone else going about this? I'm always open to new ideas. Thx
http://www.homedepot.com/p/Raco-Retr...-936/203743171

This ^^^ is the kind of old work box suited for pendants.

If a beam is right in the way -- go with a classic pancake -- perhaps with some additional blocking.
telsa is offline   Reply With Quote
Old 06-24-2015, 11:57 PM   #7
Senior Member
 
Join Date: May 2014
Location: youfigureitout
Posts: 112
Rewards Points: 184
Default

I'm only having this issue in 1 town, he told me if i was gonna old work them, i had to use a fan support box or a pancake right on the joist. Than I bet he bangs me for box fill with the pancake since they're daisy chained.
NJSparky is offline   Reply With Quote
Old 06-24-2015, 11:59 PM   #8
Senior Member
 
Join Date: May 2014
Location: youfigureitout
Posts: 112
Rewards Points: 184
Default

Quote:
Originally Posted by telsa View Post
http://www.homedepot.com/p/Raco-Retr...-936/203743171

This ^^^ is the kind of old work box suited for pendants.

If a beam is right in the way -- go with a classic pancake -- perhaps with some additional blocking.
Thx, this is exactly the sort of thing I was looking for.
NJSparky is offline   Reply With Quote
Old 06-25-2015, 03:25 AM   #9
Senior Member
 
Join Date: May 2015
Location: Sacramento, California
Posts: 14,057
Rewards Points: 26,360
Default

Quote:
Originally Posted by NJSparky View Post
I'm only having this issue in 1 town, he told me if i was gonna old work them, i had to use a fan support box or a pancake right on the joist. Than I bet he bangs me for box fill with the pancake since they're daisy chained.
There's a general tendency to forget that many listed fixtures actually have a cubic inch allowance for conductors -- THEMSELVES.

In this, they are very much like mud rings/ plaster rings -- which also have a cubic inch allowance.

You may have to poke around, but the typical pendant has as much wire space to work with as the pancake, itself. When this is true, daisy chaining 14-2 is not going to bust through the Code limit.
telsa is offline   Reply With Quote
Old 06-25-2015, 08:51 PM   #10
Senior Member
 
Join Date: May 2015
Location: Philly
Posts: 159
Rewards Points: 318
Default

Speaking of crappy blue boxes, can someone tell me what they have used this box for or if anyone has? A switch fed by a switch loop with 14/2 would still be a violation of code by exceeding the 8ci box fill? I've never seen one used.

http://t.homedepot.com/p/Carlon-1-Ga...-UPC/100404057
Jay82304 is offline   Reply With Quote
Old 06-25-2015, 09:26 PM   #11
Senior Member
 
Join Date: May 2011
Location: Northern Virginia
Posts: 1,491
Rewards Points: 864
Default

[QUOTE=Jay82304;2061202]Speaking of crappy blue boxes, can someone tell me what they have used this box for or if anyone has? A switch fed by a switch loop with 14/2 would still be a violation of code by exceeding the 8ci box fill? I've never seen one used.

I've seen a few usually used by Joe the handy man who knows no better, they usually get ripped out for the correct box.

On a different note to the OP watch the fixture canopies cubic capacity. Doesn't it have to be stamped inside somewhere? Just saying as the inspector sounds like a d#ck.
__________________
Pride is doing what you know is right especially when no one else is looking.
Sparky J is offline   Reply With Quote
The Following User Says Thank You to Sparky J For This Useful Post:
danhasenauer (06-27-2015)
Old 06-25-2015, 09:54 PM   #12
Senior Member
 
LawnGuyLandSparky's Avatar
 
Join Date: Nov 2007
Posts: 6,380
Rewards Points: 172
Default

Quote:
Originally Posted by NJSparky View Post
I'm only having this issue in 1 town, he told me if i was gonna old work them, i had to use a fan support box or a pancake right on the joist. Than I bet he bangs me for box fill with the pancake since they're daisy chained.
I suggest you either hone your ceiling layout skills and eliminate the problem alltogether
LawnGuyLandSparky is offline   Reply With Quote
Old 06-25-2015, 10:08 PM   #13
Senior Member
 
ponyboy's Avatar
 
Join Date: Nov 2012
Location: parts unknown
Posts: 8,051
Rewards Points: 709
Default

Quote:
Originally Posted by IslandGuy View Post
I suggest you either hone your ceiling layout skills and eliminate the problem alltogether

Ten four. Buy a laser bob and tell those ****ers you're laying out the ceiling with the plans you were given and if it changes there will be charges. If they're that high end they shouldn't mind paying you to get the pendants right on the nuts.


Sent from my iPad using Tapatalk
__________________
Too dumb for New York, too ugly for LA
ponyboy is offline   Reply With Quote
Old 06-25-2015, 11:01 PM   #14
Member
 
Join Date: Mar 2014
Location: OK
Posts: 39
Rewards Points: 84
Default

What about the allied flange boxes

http://www.alliedmoulded.com/catalog...rt-boxes/9305/
tceek is offline   Reply With Quote
Old 06-25-2015, 11:17 PM   #15
Junior Member
 
canadian-dj's Avatar
 
Join Date: Oct 2011
Location: Alberta, canada
Posts: 23
Rewards Points: 14
Default

Quote:
Originally Posted by ponyboy View Post

Ten four. Buy a laser bob and tell those ****ers you're laying out the ceiling with the plans you were given and if it changes there will be charges. If they're that high end they shouldn't mind paying you to get the pendants right on the nuts.

Sent from my iPad using Tapatalk
I was just about to say this
canadian-dj is offline   Reply With Quote
Old 06-25-2015, 11:20 PM   #16
Petulant Amateur
 
99cents's Avatar
 
Join Date: Aug 2012
Location: Perky Nipples, Canada
Posts: 21,229
Rewards Points: 12,825
Default

Quote:
Originally Posted by ponyboy View Post
Ten four. Buy a laser bob and tell those ****ers you're laying out the ceiling with the plans you were given and if it changes there will be charges. If they're that high end they shouldn't mind paying you to get the pendants right on the nuts.


Sent from my iPad using Tapatalk
Exactly. If they want it moved after the fact, it's a service call and they can do the patching.

Laser plumbs rock .
99cents is online now   Reply With Quote
Old 06-26-2015, 01:29 AM   #17
Senior Member
 
backstay's Avatar
 
Join Date: Feb 2011
Location: mn
Posts: 12,376
Rewards Points: 296
Default

Quote:
Originally Posted by tceek View Post
How is that going in as old work?
backstay is offline   Reply With Quote
Old 06-26-2015, 05:15 PM   #18
Jesus Scott
 
electricmanscott's Avatar
 
Join Date: Feb 2010
Location: Massachusetts
Posts: 9,383
Rewards Points: 232
Default

Boxes for ceiling fixtures have to be rated to support 50 pounds minimum. I don't think I've seen an old work box that has that rating. 314.27(A)(2)
__________________
Quote:
Life is hard
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
electricmanscott is offline   Reply With Quote
Old 06-26-2015, 07:24 PM   #19
Senior Member
 
Join Date: May 2015
Location: Sacramento, California
Posts: 14,057
Rewards Points: 26,360
Default

Quote:
Originally Posted by Jay82304 View Post
Speaking of crappy blue boxes, can someone tell me what they have used this box for or if anyone has? A switch fed by a switch loop with 14/2 would still be a violation of code by exceeding the 8ci box fill? I've never seen one used.

http://t.homedepot.com/p/Carlon-1-Ga...-UPC/100404057
For LV use, and not too many of those.

You'd go that way if there was a filthy stud bay (retro re-hab) and you wanted to box-in for a door-bell/ intercom/ CAT 5e -- and shield the connection from falling junk.

It also can handle a 14-2 switch-leg:

In 2"
Out 2"
Yoke 2"
Ground 2"
Sum: 8"

No neutral, of course.

It's a size shunned by ECs, of course.
telsa is offline   Reply With Quote
Old 06-26-2015, 07:35 PM   #20
Senior Member
 
Join Date: May 2015
Location: Sacramento, California
Posts: 14,057
Rewards Points: 26,360
Default

Quote:
Originally Posted by electricmanscott View Post
Boxes for ceiling fixtures have to be rated to support 50 pounds minimum. I don't think I've seen an old work box that has that rating. 314.27(A)(2)

"Brace is designed for maximum support load of 75 lbs. ceiling fans or 110 lbs. light fixture on 16 in. joist span."


http://www.homedepot.com/p/Raco-Retr...-936/203743171

Strictly speaking, this IS an old work box designed for cutting in.

The technique presumes a hole-saw penetration -- and then the gadget is worked up and through the hole -- the arm, first -- and cranked into position between the lumber. This puppy can even reach out to 24" O.C. joists.

Its design causes it to sit -- just 'so' -- Then the box itself is anchored to the bracing bar -- which then puts the face of the box in the correct spot.

Before the box is shoved up, the Romex is stubbed into it, some slack is permitted in old work situations, of course.

&&&&&&

Many j-men could go years at a stretch without touching one of these puppies. They really are a one-trick pony.

Wall sconces use a different old work box entirely, as the brace is no help in a wall cavity.
telsa is offline   Reply With Quote
The Following User Says Thank You to telsa For This Useful Post:
stevek (07-20-2015)
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off


Similar Threads
Thread Thread Starter Forum Replies Last Post
Fixture support... T&K General Electrical Discussion 9 05-21-2014 04:48 PM
Fixture support Magnettica General Electrical Discussion 12 03-01-2012 10:53 PM
junction box support. kaboler Canadian Electrical Forum 17 11-20-2011 09:17 PM
Box Support rlc3854 NEC Code Forum 7 02-09-2011 09:39 AM
box support voltz General Electrical Discussion 6 09-13-2010 02:02 AM


All times are GMT -4. The time now is 05:23 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2019, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2019 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com