Old 05-14-2020, 11:37 AM   #1
SRG
Junior Member
 
Join Date: May 2020
Location: Gill, MA
Posts: 1
Rewards Points: 2
Default Detached Garage - GROUNDING

Hey Guys,

Running a 100 AMP subpanel off meter box on the house.
I'm running 1/0 aluminum triplex.

Question: Do I need to run a ground with that or just pound ground rods at the garage? I'm not finding it in the code and I know it can be state specific. But can anybody help me out with NEC guidelines or an article to check out?

Thanks!
SRG is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 05-14-2020, 11:47 AM   #2
Senior Member
 
Bird dog's Avatar
 
Join Date: Oct 2015
Location: South East US
Posts: 6,170
Rewards Points: 2,058
Default

Since you're an apprentice, ask your jman. Secondly, this is considered DIY, since, this is on your own house. The mods will sort this out.
btw when are you going to test for your card?
__________________
EARTH FIRST! We'll strip-mine the other planets later.
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.

Popcorn munching forum observer
"The supreme art of war is to subdue the enemy without fighting." Sun Tzu

Last edited by Bird dog; 05-14-2020 at 11:50 AM.
Bird dog is online now   Reply With Quote
Old 05-14-2020, 12:03 PM   #3
Moderator

 
Dennis Alwon's Avatar
 
Join Date: May 2009
Location: Chapel Hill, NC
Posts: 21,644
Rewards Points: 2,204
Default

You need a 4 wire cable and you need ground rods. Are you doing this for yourself or someone else?

250.32
tmessner likes this.
__________________
They say I shot a man named Gray and took his wife to Italy
She inherited a million bucks and when she died it came to me
I can't help it if I'm lucky
Dennis Alwon is offline   Reply With Quote
The Following User Says Thank You to Dennis Alwon For This Useful Post:
Bird dog (05-14-2020)
Sponsored Links
Advertisement
 
Old 05-14-2020, 12:13 PM   #4
Senior Member
 
HackWork's Avatar
 
Join Date: Oct 2009
Location: N/A
Posts: 38,021
Rewards Points: 1,283
Default

Quote:
Originally Posted by SRG View Post
I'm not finding it in the code and I know it can be state specific.
Yes, which is why you need to know the exact code in the state you are working before you do anything.
tmessner and Bird dog like this.
__________________

To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.
HackWork is online now   Reply With Quote
Old 05-14-2020, 03:57 PM   #5
Senior Member
 
Join Date: Mar 2010
Location: NH
Posts: 1,353
Rewards Points: 2,895
Default

This place really needs the 3 question quiz like @Majewski has over at C. B. E.
__________________
Kevin for Moderator
Swampy doesn't want the job
* Make Electriciantalk Great Again! *
JoeSparky is online now   Reply With Quote
Old 05-14-2020, 04:16 PM   #6
Senior Member
 
Bird dog's Avatar
 
Join Date: Oct 2015
Location: South East US
Posts: 6,170
Rewards Points: 2,058
Default

Quote:
Originally Posted by JoeSparky View Post
This place really needs the 3 question quiz like @Majewski has over at C. B. E.
Nah...a one time nuisance charge with a major credit card.
John Valdes and Easy like this.
__________________
EARTH FIRST! We'll strip-mine the other planets later.
To view links or images in signatures your post count must be 10 or greater. You currently have 0 posts.

Popcorn munching forum observer
"The supreme art of war is to subdue the enemy without fighting." Sun Tzu
Bird dog is online now   Reply With Quote
Old 05-19-2020, 09:42 AM   #7
cool cat
 
Join Date: Dec 2008
Location: minnesota
Posts: 277
Rewards Points: 335
Default

If your coming off a meter base with add on lugs( before any mains) to a detached garage, isnt it ok to run a 3 wire and drive ground rods at the garage.
mbednarik likes this.
dogleg is offline   Reply With Quote
Old 05-19-2020, 10:28 AM   #8
Moderator

 
Dennis Alwon's Avatar
 
Join Date: May 2009
Location: Chapel Hill, NC
Posts: 21,644
Rewards Points: 2,204
Default

Quote:
Originally Posted by dogleg View Post
If your coming off a meter base with add on lugs( before any mains) to a detached garage, isnt it ok to run a 3 wire and drive ground rods at the garage.
In that case it would be compliant. I didn't realize that was what the op was asking. I assumed a meter main
__________________
They say I shot a man named Gray and took his wife to Italy
She inherited a million bucks and when she died it came to me
I can't help it if I'm lucky
Dennis Alwon is offline   Reply With Quote
Old 05-19-2020, 10:58 AM   #9
cool cat
 
Join Date: Dec 2008
Location: minnesota
Posts: 277
Rewards Points: 335
Default

yep I assumed it was just the meter base but it could be either.
Here in our part of the country fewer and fewer on the house and a meter/panel combo at pole.As long as no other breaker spaces except main 200 amp breaker we can run a 3 wire. Weve gone back and forth on this rule so the poco changed to just a meter and a main to avoid service inspections.
I have heard rumors that a main breaker will be required on the outside of the house for 2020 NEC.I wonder if this disconnect on the pole sometimes 200 feet away will satisfy this rule?
dogleg is offline   Reply With Quote
Old 05-19-2020, 02:23 PM   #10
Senior Member
 
Join Date: Apr 2013
Location: rural mn
Posts: 450
Rewards Points: 908
Default

Our code classes said that will qualify as the "emergency disconnect". Midwest Electrical Seminars
dogleg likes this.
tmessner is offline   Reply With Quote
Reply

Tags
detached garage, grounding

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off



All times are GMT -4. The time now is 10:39 AM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2020, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com