Service entrance rated transfer switch accompanying back up generator...

Most economical is to access the Utility's side / meter compartment and come directly off the load side of the meter (buss) removing the factory installed interconnecting wires (meter load buss to customer side main breaker) and replacing with wire to Utility side of transfer switch...

Is this ever done ? piping out of the meter section, (this would be less than 2 feet)
Will the Utility allow ?
WLY.G is offline   Reply With Quote
Join Contractor Talk

Join the #1 Electrician Forum Today - It's Totally Free!

ElectricianTalk.com - Are you a Professional Electrical Contractor? If so we invite you to join our community and see what it has to offer. Our site is specifically designed for you and it's the leading place for electricians to meet online. No homeowners asking DIY questions. Just fellow tradesmen who enjoy talking about their business, their trade, and anything else that comes up. No matter what your specialty is you'll find that ElectricianTalk.com is a great community to join. Best of all it's totally free!

Join ElectricianTalk.com - Click Here JOIN FOR FREE


Warning: The topics covered on this site include activities in which there exists the potential for serious injury or death. ElectricianTalk.com DOES NOT guarantee the accuracy or completeness of any information contained on this site. Always use proper safety precaution and reference reliable outside sources before attempting any construction or remodeling task!

Sponsored Links
Advertisement
 
Old 11-02-2019, 03:54 PM   #2
Moderator

 
Dennis Alwon's Avatar
 
Join Date: May 2009
Location: Chapel Hill, NC
Posts: 21,704
Rewards Points: 2,302
Default

I am confused. Do you have a meter / anin or just a meter?
__________________
They say I shot a man named Gray and took his wife to Italy
She inherited a million bucks and when she died it came to me
I can't help it if I'm lucky
Dennis Alwon is online now   Reply With Quote
Old 11-03-2019, 12:52 PM   #3
Junior Member
 
Join Date: Nov 2019
Location: Antelope Valley, CA.
Posts: 4
Rewards Points: 8
Default

Hey Dennis, Yes combo - meter / Utility in one side and customer / breakers in the other side
WLY.G is offline   Reply With Quote
Sponsored Links
Advertisement
 
Old 11-04-2019, 08:41 AM   #4
Moderator

 
Dennis Alwon's Avatar
 
Join Date: May 2009
Location: Chapel Hill, NC
Posts: 21,704
Rewards Points: 2,302
Default

I don't think this would be allowed as you are modifying the equipment, however it is often done when you have a meter with a separte panel. I would ask the authority having jurisdiction. IMO, there is nothing unsave about it but some inspectors can be tough on it.

Also if you do that then the wires in the meter main would have to be treated as in a sub panel so is it possible to isolate the neutral from the ground.

The equipment may also only be rated as service equipment in which case you cannot do what you are planning
__________________
They say I shot a man named Gray and took his wife to Italy
She inherited a million bucks and when she died it came to me
I can't help it if I'm lucky
Dennis Alwon is online now   Reply With Quote
Reply

Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are Off
Refbacks are Off



All times are GMT -4. The time now is 03:42 PM.


Powered by vBulletin® Version 3.8.8
Copyright ©2000 - 2020, vBulletin Solutions, Inc.
Search Engine Optimization by vBSEO 3.6.1
vBulletin Security provided by vBSecurity v2.2.2 (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
User Alert System provided by Advanced User Tagging (Pro) - vBulletin Mods & Addons Copyright © 2020 DragonByte Technologies Ltd.
Our Pro Sites Network
ContractorTalk.com | DrywallTalk.com | HVACSite.com | PaintTalk.com | PlumbingZone.com | RoofingTalk.com